SYSTEM ROLE
Sixteen commoned 24 VDC output terminations
The 9662-610 panel connects field loads to the documented 24 VDC digital-output module arrangement. Its 16 load points and commoned power connections form a field-termination interface, separate from the output module and interface cable.
The guide lists models 3624, 3625, 3664 and 3674 for this panel. The general panel total is 16 A, but the 3625 application is limited to 10 A per panel to control module power dissipation. Use the panel with self-protected modules only.