SYSTEM ROLE
Protected DC switching for 16 output points
The 1756-OB16E switches 12/24V DC field loads from the 1756 platform I/O system. Its sixteen sourcing outputs are divided into two groups of eight, with electronic fusing per group and output/fuse status available to the controller.
The module occupies one chassis slot and accepts a 1756-TBNH or 1756-TBSH removable terminal block. Select the terminal block, field supply and load currents together; individual outputs within a group are not isolated from each other.