SYSTEM ROLE
Eight differential analog measurement channels
The EM AE08 extends an S7-200 SMART station with eight analog inputs. The documented ranges are ±10 V, ±5 V, ±2.5 V and 0 to 20 mA. Voltage or current operation is selected in pairs of channels, so the configured range and paired-channel arrangement must match the connected sensors.
The module uses 24 V DC field power and the expansion bus. Its specified resolution is 12 bits plus sign in voltage mode and 12 bits in current mode. Record the installed CPU, measurement range, filter settings and transducer wiring when requesting a replacement.