SYSTEM ROLE
Fused commoned 115 V digital-input termination
The manufacturer cross-reference maps 3000510-180 to termination-panel model 9561-810 and interface cable 4000093-110. The panel has 16 input points and commoned PWR+ and PWR− terminals for the documented 115 V digital-input arrangement.
Models 3501E and 3501T are listed with 32 points, requiring two 16-point panels per input module. Each input point is fuse-protected with a blown-fuse indicator. Match AC/DC field wiring and the correct module and cable before ordering.