SYSTEM ROLE
Isolated current input with HART communication
AAI143 converts sixteen 4–20 mA field signals into control-system data. Its isolation is between the input side and the system; this is distinct from the individually isolated channels of AAI135.
The -H version adds HART digital communication. Two-wire or four-wire transmitter wiring is set for each channel by setting pins. Terminal, cable and redundant-module choices must match the receiving FIO node and field-circuit design.