SYSTEM ROLE
Current-signal acquisition for rack I/O
DAI 01 acquires 16 analog-current channels in the 0–20 mA or 4–20 mA ranges. ABB specifies a 50-ohm input impedance and 12-bit conversion, with two optoisolated groups of eight channels. It is distinct from the DAI 02 voltage-input and DAI 03 higher-impedance current-input types.
The module self-scans with a configurable cycle time of 10 ms or slower. Current-range alarms, channel indicators and line-break evaluation depend on the selected range and controller engineering. Preserve channel assignments, grounding and signal configuration when replacing the module.