SYSTEM ROLE
Switch AC or DC loads through relay contacts
The module provides 16 Form A normally open outputs. Channels 0–7 share Common 0 and channels 8–15 share Common 1. AC and DC devices can be used on separate groups, but do not mix power types on channels sharing the same common.
The supplied photograph identifies Series A. Its electronics draw from both MOD and DC SA power. Later Series C has different supply consumption, so match the actual hardware series rather than applying one set of power values to every 5069-OW16.