SYSTEM ROLE
Multi-loop process control and information processing
The IMMFP12 executes configured control functions and handles data acquisition and information processing. The documented I/O expander bus supports up to 64 low-power I/O modules in a module mounting unit.
A separate 1 Mbaud redundancy link connects primary and backup processors. Match both firmware revisions and the installed termination arrangement; redundancy is a system configuration and is not included by ordering one module.